UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A & INSTALLATION / OWNER’S MANUAL Improper installation, adjustment, alteration, ser
10 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A Installation must conform with all local, state, provincial and national code requirem
11 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A MODEL RECOMMENDED MOUNTING HEIGHT RANGE* ft (m) MAXIMUM DISTANCE BETWEEN HEATERS ft
12 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 7. SYSTEMS INCORPORATING 90° ELBOWS AND 180° ELBOWS The radiant tube heater can be ins
13 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 8. SUSPENDING THE SYSTEM - GENERAL - details in Section 9 Inadequate or improper suspe
14 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A FIGURE 7 HANGER POSITIONING / SPACING (Also see Page 41) POSITION BURNER END HANG
15 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 9. INSTALLATION OF TUBE/REFLECTOR SYSTEM PRIOR TO PROCEEDING with the tube installati
16 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A Locate the second hanger within 6 to 24 inches (15 to 60 cm) from the swaged end of
17 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 10) At the burner end, install the reflector end cap inside of the extended inner ref
18 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A sion under the first reflector - mate snuggly with the first reflector 20) Through the
19 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A TOOLS REQUIRED Screw driver or similar tool with a shaft to aid in alignment of rive
2 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A NOTICE: This manual is current for this product. Occasional revision of the product Ce
20 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A TOOLS REQUIRED Screw driver or similar tool with a shaft to aid in alignment of rive
21 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A PROVIDE ACCESS FOR SERVICE OR REPAIR TO BURNER: MINIMUM 6 INCHES (15 CM) FROM THE ACCE
22 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 11. FLUE VENTING Inadequate venting of a heater may result in asphyxiation, carbon
23 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A HORIZONTAL VENT THROUGH THE SIDEWALL: The flue vent system must slope downwards app
24 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A Use approved 4" (10 cm) (JA-0528-XX) or 6" (15 cm) (JA-0529-XX) horizonta
25 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A VERTICAL VENT THROUGH THE ROOF: It is the sole responsibility of the installer to adh
26 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 12. COMBUSTION AIR DUCTING An opening is located on the top surface of the burner hou
27 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 13. GAS SUPPLY - HEATER EXPANSION - FLEXIBLE GAS CONNECTION The gas supply must be ins
28 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A NOTE: Access to the manifold pressure test port is on the top of the valve. A 3/16&quo
29 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A The flue vent, and combustion air duct (if installed) must also be configured in such
3 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A TABLE OF CONTENTS TOPIC ...PAGE IMPO
30 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 14. ELECTRICAL AND THERMOSTAT WIRING (WIRING DIAGRAMS PAGES 31 & 32) The heat
31 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 18. FENWAL DSI: WIRING DIAGRAM: 24V OR 120 VOLT THERMOSTAT OPERATION SINGLE HEATER P
32 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 19. MULTIPLE TUBE HEATERS per THERMOSTAT
33 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 20. FENWAL DSI: SEQUENCE OF OPERATION / FLAME RECOVERY / SAFETY LOCKOUT Power Up / Sta
34 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A Flame Fault If at any time the main valve fails to close completely and maintains a f
35 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A USE THE BLACK BARS BELOW AS A GUIDE FOR AD-JUSTMENT. USE THE BARS THAT COINCIDE W
36 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 21. TROUBLESHOOTING GUIDE - FENWAL DSI (also see Heater Troubleshooting next page) SY
37 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 22. TROUBLESHOOTING GUIDE WARNING Improper adjustment, alteration, service or mainten
38 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A MAIN BURNER LIGHTS SYSTEM RUNS UNTIL CALL FOR HEAT ENDS CALL FOR HEAT ENDS: SYSTEM SH
39 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A WARNING START UP ‘SMOKE’ During start up, material coatings used in the production
4 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A APPLICATION This appliance has been certified by CSA International to ANSI Z83.20 / CSA
40 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A TYPE OF GAS: NG LP DOES BUILDING HAVE A NEGATIVE CONDITION: YES NOIF THIS IS A HIG
41 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A Manufactured and shipped in 10 ft lengths. Swaged tube has approximate 4 inch (
42 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A BEST RANGES FOR HANGER LOCATION: DISTANCE IN INCHES FROM FLANGE AT BURNER END Tube #
43 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A HANGER / REFLECTOR ORIENTATION HORIZONTAL TO 350 (at 30°) Tube Length ‘L’ = center
44 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 26. BURNER & TUBE KIT ASSEMBLY CHART MODELS UHE, EIH MODELS UHE & EIH are ap
45 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A MODEL NO STD ORIFICE Drill Size / Part# FOR USE AT ALTITUDES ABOVE (FEET) 2000 3000 4
46 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 28. OPTIONAL ACCESSORIES Flue Vent Terminal 4” wall horizontal 6” wall horizontal JA
47 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 90 degree Aluminized Steel Elbow Kit* *Kit includes: elbow, tube coupler, and reflect
48 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A TruTemp Thermostat True comfort control for radiant heating systems - senses and avera
49 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A UHE / EIH Burner 29. BURNER PARTS LIST # PART NAME PART # PART DESCRIPTION
5 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A Heater Expansion It is a normal condition that during heat-up and cool-down a tube hea
50 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A # PART DESCRIPTION PART # PART DESCRIPTION SUPPLEMENT 14 IGNITER KIT JA-0571-KT Sp
51 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 30. TUBE SYSTEM PARTS LIST # PART DESCRIPTION PART # PART DESCRIPTION PRIMARY SUP
52 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A HONEYWELL S87J DSI: WIRING DIAGRAM: 24V OR 120 VOLT THERMOSTAT OPERATION SINGLE HEATE
53 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A HONEYWELL S87J: SEQUENCE OF OPERATION The S87 ignition control module is powered by a
54 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A LIMITED WARRANTY CERTIFICATE FOR GAS-FIRED INFRA-RED LOW INTENSITY TUBE HEATERS: UHE a
6 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A Clearance to combustibles Location of flammable or explosive objects, liquids or vapor
7 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A TABLE 1 MINIMUM CLEARANCES TO COMBUSTIBLES* (measured from the hanger) FIGURE 1 MINIM
8 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A VENT END CLEARANCE: Clearances from the vent pipe are determined by local or national i
9 UHE-F / EIH-F I&O Manual IM100205 RD: MAY 2014 RL: 06A 3. INSTALLATION IN COMMERCIAL GARAGES AND PARKING STRUCTURES Low Intensity Heaters