GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH INSTALLATION /OWNER’S MANUAL 2300 & IO-210 SERIES HIGH EFFICIENC
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH Page 6 WALL MOUNTING BRACKET ARM MOUNTING BRACKET (WITH GAS HOSE AND WIRING) CHAIN HA
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH Diagram 4: 2300 MOUNTING ARM TEMPLATE Page 7
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH Diagram 5: 2300 WALL BRACKET TEMPLATE Page 8
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH 1. Install the Wall Mount Bracket on the wall, using four bolts...(not supplied). S
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH Page 10 Diagram 7: SERVICING HEATER
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH Note: Do not store or place anything directly under heater Page 11 MODEL NO Ends Hor
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH 8.5 SUGGESTED MOUNTING DISTANCES FOR COMFORT Mounting Parameters *** MODELS 2312
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH 10. SEQUENCE OF OPERATION: HONEYWELL S87C DSI CONTROL (See page 19 for FENWAL Control
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH 11. WIRING DIAGRAM FOR 2300 / IO 210 SERIES with Honeywell S87C DSI Control (Se
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH LOW/ UNSTEADY FLAME CURRENT If the current to the S87C flame circuit is less than 1.5
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH NOTICE: The manufacturer reserves the right to make changes to equipment and specifi
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH 13. TROUBLESHOOTING GUIDE TURN HEATER ON : (AT PATIO CONTROL PANEL IF INSTALLED) 2
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH MAIN BURNERS LIGHT SPARK STOPS WHEN BURNERS ARE LIT. DOES FLAME REMAIN STABLE AFTER
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH Fault Conditions: The LED will flash on for 1/4 second, then off for 1/4 second durin
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH Start up - Heat Mode: On a call for heat the Fenwal 35-60 control will reset, perfor
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH 16. SPARK IGNITION CIRCUIT The step-up transformer in the ignition control provides
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH COMMISSIONING REPORT AS PER I&O MANUAL AND
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH Page 22 TO BE COMPLETED BY THE LICENSED INSTALLER:
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH 18. Replacement Parts List Only the following illustrated parts are available. For
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH Some Authorities do not allow certain warranty exclusions or limitations on how long
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH TABLE OF CONTENTS TOPIC PAGE NUMBER 1. GENERAL ...
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH Important notice To Installer: Installation and repairs should be done by a qualifi
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH 1. GENERAL 2. INSTALLATION REQUIREMENTS 2.1 MOUNTING CLEARANCES Series 2300 / IO 2
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH CAUTION: DO NOT INSTALL ANY GAS PIPING IN HEAT ZONES. The maximum supply pressure
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH 5. SHUT DOWN INSTRUCTIONS a) For temporary shutdown, turn off the electrical circuit
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH Cause & remedy of back firing: • Improper gas pressure entering the ve
GP-M230-BX-06A 2300 / IO 210 Manual RD: Sept, 2005 R.L. 6 KH Page 5 MODEL Voltage VAC Current amps Btu/hr input Total Weight (lbs). Length <