P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A INSTALLATION / OWNER’S MANUAL Improper installation, adjustment, alteration, service
10 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A WARNING Improper installation, adjustment, alteration, service or maintenance can ca
11 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A Proximity of lights, sprinkler heads, overhead doors, storage areas, gas and electri
12 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A IMPORTANT: Single or multiple heater placement must be such that continuous operatio
13 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 2. Connect to the structure using mechanically sound means to support the weight. E
14 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A For 30° angle mount: Remove burner (4 bolts + spark wire); Install the tube system;
15 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A FIGURE 6 P40U MINIMUM CLEARANCES TO COMBUSTIBLES It is the installer’s responsibil
16 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 8-A SEISMIC RESTRAINT - LATERAL AND LONGITUDINAL PLANES In areas prone to earthqua
17 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A WARNING 9. FLUE VENTING Inadequate venting of a heater may result in asphyxiati
18 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A HORIZONTAL VENT THROUGH A SIDE WALL: Maximum allowable flue vent length is equiva
19 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A Termination Cap Options: Use the approved 4" (10 cm) (JA-0528-XX) or 6&q
2 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A NOTICE: This manual is current for this product. Occasional revision of the product
20 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A VERTICAL VENT THROUGH THE ROOF: It is the sole responsibility of the installer to ad
21 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A Optional 4 inch intake terminals are available for this heater: Part number: JS-0
22 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A DO NOT use pressure greater than 1/2 psig to pressure check the heater. During any p
23 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 12. GAS CONVERSION WARNING: Gas conversion must only be performed by a trained gas
24 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 13. ELECTRICAL AND THERMOSTAT WIRING (WIRING DIAGRAMS PAGE 26 & 27) The hea
25 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 18. FENWAL DSI: WIRING DIAGRAM: 24V OR 120 VOLT THERMOSTAT OPERATION SINGLE HEATER
26 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 18. MULTIPLE TUBE HEATERS per THERMOSTAT (ALL DSI TYPES) Each tube heater requires
27 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 19. FENWAL DSI: SEQUENCE OF OPERATION / FLAME RECOVERY / SAFETY LOCKOUT Power Up / S
28 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A Flame Fault If at any time the main valve fails to close completely and maintains a
29 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A SERVICE CHECKS Flame current passes through the flame from the sensor to ground. Th
3 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A TABLE OF CONTENTS IMPORTANT INFORMATION - READ FIRST APPLICATION...
30 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A Each tube heater requires 120V, 60 HZ electrical power sized for 145VA. The heate
31 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 21. P40U-P (-IP), P40U-W (-IW) SEQUENCE OF OPERATION GASLITER 50N (DSI) The Gasliter
32 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 22. IGNITION CONTROL: MODELS P40U-P, -W (-IP, -IW) - GASLITER MICRO 50N The MICRO 5
33 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A Loss of Flame - Spark Restoration Retrial If there is a loss of flame during the run
34 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A USE THE BLACK BARS BELOW AS A GUIDE FOR AD-JUSTMENT. USE THE BARS THAT COINCIDE
35 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 24. TROUBLESHOOTING GUIDE — HEATER OPERATION — FENWAL DSI Improper adjustment, alte
36 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A MAIN BURNER LIGHTS SYSTEM RUNS UNTIL CALL FOR HEAT ENDS CALL FOR HEAT ENDS: SYSTEM
37 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 25. START-UP / COMMISSIONING SHEET COMMISSIO
38 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A TYPE OF GAS: NG LP DOES BUILDING HAVE A NEGATIVE CONDITION: YES NOIF THIS IS A H
39 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A Assembled System: Weight: 86 pounds (39 kg) Dimensions: 119.5” L x 20” W x 12”
4 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A INSPECT PRODUCT UPON RECEIPT Inspect the carton and heater for concealed damage. Note
40 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A ORIFICE CHART - ALTITUDE CONVERSION MODEL NO FOR USE AT ALTITUDES ABOVE (FEET) Gas
41 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 28. OPTIONAL ACCESSORIES Flue Vent Terminal 4” wall horizontal 6” wall horizontal
42 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A #2 Lion Chain (115 lb work load) - 200 ft roll Safety Snap Hooks - 2” - pkg of 25
43 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A JS-0502-UR-GK PROTECTIVE GUARD SCREEN OPTION – Zinc Plated; Two Piece Kit – Re
44 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A Fig.5 Fig. 6 STEP 4: On the second side of the reflector, first Insert a guard pin
45 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 29. REPLACEMENT PARTS LIST P40U BURNER # PART DESCRIPTION PART # PART DESCRIPTION PR
46 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A # PART DESCRIPTION PART # PART DESCRIPTION PRIMARY SUPPLEMENT 23 INDICATOR LAMPS JW
47 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 30 TUBE FASTENING BRACKET JS-0502-UV Positions tube in hanger / reflector system 3
48 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A HONEYWELL S87-J WIRING DIAGRAM P40U, P40U-I : 24V OR 120 VOLT THERMOSTAT SINGLE HE
49 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A HONEYWELL S87J: MODELS P40U, P40U-I SEQUENCE OF OPERATION The S87 ignition control
5 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A Heater Expansion It is a normal condition that during heat-up and cool-down a tube h
50 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A LOW/ UNSTEADY FLAME CURRENT If the current to the S87 flame circuit is less than 1.5
51 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A LIMITED WARRANTY CERTIFICATE FOR GAS-FIRED INFRA-RED LOW INTENSITY TUBE HEATERS: P40
6 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A Clearance to combustibles Location of flammable or explosive objects, liquids or vap
7 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A FIGURE 1 MINIMUM CLEARANCES TO COMBUSTIBLES* - Table 1 lists values *The clearance t
8 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A VENT END CLEARANCE: Clearances from the vent pipe are determined by local or national
9 P40U-F / P40U-IF I&O Manual IM101220 RD: JAN 2014 RL: 4A 2. INSTALLATION IN COMMERCIAL AIRCRAFT HANGARS Low intensity radiant tube heaters ar