ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA Gas-Fired Luminous (High Intensity) Infrared Heaters INSTALLATION / OWNER’S MA
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 10 3. INSTALLATION IN COMMERCIAL GARAGES AND PARKING STRUCTURES Luminous (hi
11 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 6. MOUNTING CLEARANCES This heater must be mounted with at least the minimum
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 12 SUSPENDED HORIZONTALLY: (long axis level) TABLE 2: SUGGESTED LAYOUT / MOUNT
13 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 8. VENTILATION Inadequate venting of a heater may result in asphyxiation,
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 14 WARNING 9. GAS SUPPLY PIPING A. Gas piping must be sized to provide adeq
15 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA GAS SUPPLY PRESSURE: The maximum supply pressure must be limited to 14 inches
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 16 11.1 GAS VALVE ASSEMBLY TO VENTURI 1. Remove valve and heater from carton.
17 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA S S 11.2 HEATER SUSPENSION A. Properly size and install ventilation as per
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 18 G. In locations used for the storage of combustible materials, signs shall b
19 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA FIGURE 7: DIMENSIONS: ecoSchwank-X & IL TABLE 4: DIMENSIONS / WEIGHT / CA
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 2 NOTICE: This manual is current for this product. Occasional revision of the p
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 20 12. LIGHTING INSTRUCTIONS A Open the isolation valve in the main gas line
21 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 14. ELECTRICAL WIRING DIAGRAM - 24V CONTROL AA2 24H1 …..
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 22 15. ELECTRICAL WIRING DIAGRAM - LINE VOLTAGE (120V) CONTROL AA2 24H1 …..
23 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 16. SERVICE GUIDE Conduct a maintenance inspection of a luminous heater at
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 24 17. TROUBLESHOOTING GUIDE SET THERMOSTAT TO CALL FOR HEAT IS THE HEATER BURNI
25 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA IS THERE VOLTAGE (24V) TO IG-NITION CONTROL MODULE FROM TRANSFORMER ? →CHECK
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 26 IS THERE VOLTAGE FROM IGNITION CONTROL TO COMBINATION GAS VALVE? →C
27 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 18. HIGH ALTITUDE INSTALLATION This heater not to be installed at altitude ab
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 28 19. SEQUENCE OF OPERATION FOR FENWAL DSI CONTROL OPERATION Upon applying po
29 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA INSTALLING CONTRACTOR: ……………………………………………………………. COMMISSIONING TECHNICIAN: ………
3 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA ecoSchwank-X 36, 52 & IL-X 150, 200 GAS FIRED LUMINOUS INFRA-RED HEATERS T
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 30 TO BE COMPLETED BY THE LICENSED INSTALLER:
31 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA JX-0253-XC-A JX-0252-XC-A JX-0253-XD-A JX-0252-XD-A JL-0772-XX
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 32 JL-0771-XX JO-0368-XX JM-0300-XX JL-0776-XX J
33 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 22. PARTS LIST 1 NOTE: ECO 36 / IL 150 IS AN ASSEMBLY OF TWO ECO 18 / IL 75 B
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 34 22. PARTS LIST ecoSchwank-X / IL-X MODELSITEM1 BURNER BODY ~ INCLUDES TILES M
35 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 22. PARTS LIST - continued ecoSchwank-X & IL-X MODELS - continuedITEM14
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 36 GAS-FIRED INFRA-RED LUMINOUS SERIES: ECOSCHWANK / IL SERIES The Manufacture
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 4 APPLICATION A gas-fired luminous (high intensity) radiant heater may be instal
5 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA Heater Expansion It is a normal condition that during heat-up and cool-down a
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 6 Clearance to Combustibles Location of flammable or explosive objects, liquids
7 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA SUSPENDED AT 30° Max. Stack Height: ‘H’ = T - C MOUNTING CLEARANCE TO COMBUS
ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 8 In locations used for the storage of combustible materials signs must be post
9 ECO-X 36-52 / IL-X 150-200 Manual IM100116 RD: MAY 2009 RL: 05A - BA 1. GENERAL APPLICATION A gas-fired radiant heater may be installed for heatin